Simatic S7-300, analog output SM332, optically isolated, 2AO, U/I, 11/12bits resol., 20pin, remove/insert w. active backplane bus, Siemens
Image is illustrative
Simatic S7-300, analog output SM332, optically isolated, 2AO, U/I, 11/12bits resol., 20pin, remove/insert w. active backplane bus, Siemens
Code: 6ES7332-5HB01-0AB0
Price (indicative)
€287.40  /pc
Manufacturer :
Availability:
21 days
Weight:
0.2646 kg/pc
Volume:
0.001 m3/pc
Quantity (pc):
Plus sign Minus sign
 

 

Simatic S7-300, analog output SM332, optically isolated, 2AO, U/I, 11/12bits resol., 20pin, remove/insert w. active backplane bus, Siemens

Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 135 mA
from backplane bus 5 V DC, max. 60 mA
Power loss
Power loss, typ. 3 W
Analog outputs
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 10 mH
Cable length
● shielded, max. 200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit
● Conversion time (per channel) 0.8 ms
Settling time
● for resistive load 0.2 ms
● for capacitive load 3.3 ms
● for inductive load 0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH)
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-) 0.5 %
● Current, relative to output range, (+/-) 0.6 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.4 %
● Current, relative to output range, (+/-) 0.5 %
Interrupts/diagnostics/status information
Diagnostic functions Yes; Parameterizable
Substitute values connectable Yes; Parameterizable
Alarms
● Diagnostic alarm Yes; Parameterizable
Diagnostic messages
● Diagnostic information readable Yes
Diagnostics indication LED
● Group error SF (red) Yes
Potential separation
Potential separation analog outputs
● between the channels and backplane bus Yes
Isolation
Isolation tested with 500 V DC
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 117 mm
Weights
Weight 220 g
last modified: 11/21/2017
 
 