Elit logo e-Elit - leading
electronic and automation component
online distributor
Est En
Elit shopping basket
Items: Total:
0
€0.00
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Crimping Die 6T, hex, Al, 150mm², 21.39mm AF, W12mm, HTC-6022
Crimping Die 6T, hex, Al, 150mm², 21.39mm AF, W12mm, HTC-6022



Simatic DP, ET 200M Interface IM 153-4 PN IO f. max.12 S7-300 modules, ext. functions: isochroneous realtime com. Cl.1, 2, module ecchange w.o. PG, operation w.o. MMC, maintenance new IO modules supported, Siemens
Image is illustrative
Simatic DP, ET 200M Interface IM 153-4 PN IO f. max.12 S7-300 modules, ext. functions: isochroneous realtime com. Cl.1, 2, module ecchange w.o. PG, operation w.o. MMC, maintenance new IO modules supported, Siemens
Code: 6ES7153-4AA01-0XB0
Price (indicative)
€406.20  /pc
Manufacturer :
Availability:
21 days
Weight:
0.273 kg/pc
Volume:
0.001 m3/pc
Quantity (pc):
Plus sign Minus sign
 

 

Simatic DP, ET 200M Interface IM 153-4 PN IO f. max.12 S7-300 modules, ext. functions: isochroneous realtime com. Cl.1 ?2, module ecchange w.o. PG, operation w.o. MMC, maintenance new IO modules supported, Siemens

General information
Product type designation IM 153-4 PN ST
Vendor identification (VendorID) 002AH
Device identifier (DeviceID) 0302H
Supply voltage
Rated value (DC) 24 V
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) In a construction with grounded reference potential, a fuse is necessary for redundant interface modules (Recommendation: 2.5 A)
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Current consumption, max. 600 mA; with 24 V DC supply
Inrush current, typ. 4 A
I²t 0.09 A²·s
Output voltage
Rated value (DC) 5 V
Output current
for backplane bus (5 V DC), max. 1.5 A
Power loss
Power loss, typ. 6 W
Address area
Addressing volume
● Inputs 192 byte
● Outputs 192 byte
Hardware configuration
Number of modules per DP slave interface, max. 12
Protocols
Bus protocol/transmission protocol PROFINET IO
Interrupts/diagnostics/status information
Diagnostics indication LED
● for module diagnostics Yes
● Connection to network LINK (green) Yes
● Transmit/receive RX/TX (yellow) Yes
Potential separation
Potential separation exists Yes
Isolation
Isolation tested with 500 V DC
Degree and class of protection
IP degree of protection IP20
Ambient conditions
Ambient temperature during operation
● min. 0 °C
● max. 60 °C
Air pressure acc. to IEC 60068-2-13
● Installation altitude above sea level, max. 2 000 m
Dimensions
Width 40 mm
Height 125 mm
Depth 118 mm
Weights
Weight 215 g
last modified: 11/21/2017
 
 
Elit OÜ | e-post: elit@elit.ee | +372 622 9119 | 2016 ©


 
X
 