Elit logo e-Elit - leading
electronic and automation component
online distributor
Est En
Elit shopping basket
Items: Total:
0
€0.00
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
End Cover D-ST 2.5, 50pcs/pck, Phoenix
End Cover D-ST 2.5, 50pcs/pck, Phoenix



Simatic ET 200SP, Analog Input Module, 8x AI 2-/4-wire basic, fits to BU-type A0, A1, color code CC01, module diagnosis, 16bit, Siemens
Image is illustrative
Simatic ET 200SP, Analog Input Module, 8x AI 2-/4-wire basic, fits to BU-type A0, A1, color code CC01, module diagnosis, 16bit, Siemens
Code: 6ES7134-6GF00-0AA1
Price (indicative)
€201.60  /pc
Manufacturer :
Availability:
21 days
Weight:
0.0389 kg/pc
Volume:
0.0001 m3/pc
Quantity (pc):
Plus sign Minus sign
 

 

Simatic ET 200SP, Analog Iinput Module, 8x AI 2-/4-wire basic, fits to BU-type A0, A1, color code CC01, module diagnosis, 16bit, Siemens

SIMATIC ET 200SP, Analog input module, AI 8XI 2-/4-wire Basic, suitable for BU type A0, A1, Color code CC01, Module diagnostics, 16 bit
General information
Product type designation AI 8xI 2-/4-wire BA
Firmware version V1.0
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color identification plate CC01
Product function
● I&M data Yes; I&M0 to I&M3
● Measuring range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of version V13 SP1
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● Oversampling No
● MSI No
CiR – Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 25 mA; without sensor supply
Encoder supply
24 V encoder supply
● 24 V Yes
● Short-circuit protection Yes
● Output current, max. 0.7 A; total current of all encoders/channels
Power loss
Power loss, typ. 0.7 W; Without encoder supply voltage
Address area
Address space per module
● Address space per module, max. 16 byte
Analog inputs
Number of analog inputs 8; Single-ended
● For current measurement 8
permissible input current for current input (destruction limit), max. 50 mA
Cycle time (all channels), min. 1 ms; per channel
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 100 Ω; 15 bit
● -20 mA to +20 mA Yes
● Input resistance (-20 mA to +20 mA) 100 Ω; 16 bit incl. sign
● 4 mA to 20 mA Yes
● Input resistance (4 mA to 20 mA) 100 Ω; 15 bit
Cable length
● shielded, max. 200 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Interference voltage suppression for interference frequency f1 in Hz 16.67 / 50 / 60 / 4 800 (16.67 / 50 / 60)
● Conversion time (per channel) 180 / 60 / 50 / 0.625 (67.5 / 22.5 / 18.75) ms
Smoothing of measured values
● Number of smoothing levels 4; None; 4/8/16 times
● parameterizable Yes
Encoder
Connection of signal encoders
● for voltage measurement No
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 650 Ω
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. 50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %
Operational error limit in overall temperature range
● Current, relative to input range, (+/-) 0.5 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm No
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; at 4 to 20 mA
● Short-circuit Yes; Sensor supply to M; module by module
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; Green LED
● Channel status display Yes; Green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED
Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics No
Isolation
Isolation tested with 707 V DC (type test)
Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm
Weights
Weight, approx. 31 g
last modified: 11/10/2018
 
 