Elit logo e-Elit - leading
electronic and automation component
online distributor
Est En
Elit shopping basket
Items: Total:
0
€0.00
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Feed-through Terminal Block UT 4-QUATTRO BU, 50pcs/pck, Phoenix
Feed-through Terminal Block UT 4-QUATTRO BU, 50pcs/pck, Phoenix



Simatic DP, Electronics Module ET 200S, 2AI TC, W15mm, 15bit+sign ±80mV, characteristic linearization for TCs: B/E/J/K/L/N/R/S/T, cycle time 65ms/channel, SF LED (group fault), Siemens
Image is illustrative
Simatic DP, Electronics Module ET 200S, 2AI TC, W15mm, 15bit+sign ±80mV, characteristic linearization for TCs: B/E/J/K/L/N/R/S/T, cycle time 65ms/channel, SF LED (group fault), Siemens
Code: 6ES7134-4JB01-0AB0
Price (indicative)
€279.10  /pc
Manufacturer :
Availability:
21 days
Weight:
0.0473 kg/pc
Volume:
0.0001 m3/pc
Quantity (pc):
Plus sign Minus sign
 

 

Simatic DP, Electronics Module ET 200S, 2AI TC, W15mm, 15bit+sign ±80mV, characteristic linearization for TCs: B/E/J/K/L/N/R/S/T, cycle time 65ms/channel, SF LED (group fault), Siemens

Supply voltage
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 30 mA
from backplane bus 3.3 V DC, max. 10 mA
Power loss
Power loss, typ. 0.6 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input voltage for voltage input (destruction limit), max. 10 V; Permanent
Cycle time (all channels) max. Number of active channels per module x basic conversion time
Technical unit for temperature measurement adjustable No; Celsius
Input ranges
● Voltage Yes
● Current No
● Thermocouple Yes
● Resistance thermometer No
● Resistance No
Input ranges (rated values), voltages
● -80 mV to +80 mV Yes
● Input resistance (-80 mV to +80 mV) 1 MΩ
Input ranges (rated values), thermocouples
● Type B Yes
● Input resistance (Type B) 1 MΩ
● Type E Yes
● Input resistance (Type E) 1 MΩ
● Type J Yes
● Input resistance (type J) 1 MΩ
● Type K Yes
● Input resistance (Type K) 1 MΩ
● Type L Yes
● Input resistance (Type L) 1 MΩ
● Type N Yes
● Input resistance (Type N) 1 MΩ
● Type R Yes
● Input resistance (Type R) 1 MΩ
● Type S Yes
● Input resistance (Type S) 1 MΩ
● Type T Yes
● Input resistance (Type T) 1 MΩ
Thermocouple (TC)
Temperature compensation
— internal temperature compensation Not possible
— external temperature compensation with compensations socket Yes; possible, one external compensating box per channel
Characteristic linearization
● parameterizable Yes; Type B, E, J, K, L, N, R, S, T to IEC 584
Cable length
● shielded, max. 50 m
Analog value generation for the inputs
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit; 15 bit + sign
● Integration time, parameterizable Yes
● Integration time (ms) 16,7 / 20 ms
● Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
● Conversion time (per channel) 65 s; 55 / 65 ms (additional 20 ms on activated wire-break test)
Smoothing of measured values
● parameterizable Yes; In four stages by means of digital filtering
● Step: None Yes; 1x cycle time
● Step: low Yes; 4 x cycle time
● Step: Medium Yes; 32 x cycle time
● Step: High Yes; 64 x cycle time
Encoder
Connection of signal encoders
● for voltage measurement Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.6 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.4 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
● Common mode interference (USS < 2.5 V) , min. 90 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostic messages
● Diagnostic information readable Yes
● Wire-break Yes; A break in the wire is only detected for thermocouples
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 4 byte
Diagnostics wire break Disable / enable (wire break is detected only in thermocouples)
Measurement type/range Deactivated/ ±80 mV/ TC-EL Type T (Cu-CuNi)/ TC-EL Type K (NiCr-Ni)/ TC-EL Type B (PtRh-PtRh)/ TC-EL Type c (Wer-Wer) TC-EL Type N (NiCrSi-NiSi)/ TC-EL Type E (NiCr-CuNi)/ TC-EL Type R (PtRh-Pt)/ TC-EL Type S (PtRh-Pt)/ TC-EL Type J (Fe-Cu-Ni)/ TC
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Comparison point none / RTD
Comparison point number None / 1 / 2 / 3 / 4 / 5 / 6 / 7 / 8
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
Between the inputs and MANA (UCM) 2 V AC PP
between MANA and M internally (UISO) 75 V DC/60 V AC
Isolation
Isolation tested with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g
last modified: 07/04/2018
 
 