Simatic DP, Electronic Module ET 200S, 4AI 2-wire, 4..20mA, 13bit, 2-wire transducer, cycle time 40ms/ch., LED SF (ground fault), W15mm, Siemens
Image is illustrative
Simatic DP, Electronic Module ET 200S, 4AI 2-wire, 4..20mA, 13bit, 2-wire transducer, cycle time 40ms/ch., LED SF (ground fault), W15mm, Siemens
Code: 6ES7134-4GD00-0AB0
Price (indicative)
€337.20  /m
Manufacturer :
Availability:
21 days
Weight:
0.044 kg/m
Volume:
0.0001 m3/m
Quantity (m):
Plus sign Minus sign
 

 

Simatic DP, Electronic Module f. ET200S, 4AI 2-wire, 4..20mA, 13bit, W15mm, 2-wire transducer cycle time 40ms/ch., LED SF (ground fault), Siemens

Supply voltage
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 125 mA
from backplane bus 3.3 V DC, max. 10 mA
Output voltage
Power supply to the transmitters
● present Yes
● short-circuit proof Yes; approx. 200 mA for module
Power loss
Power loss, typ. 0.6 W
Address area
Address space per module
● Address space per module, max. 8 byte
Analog inputs
Number of analog inputs 4
permissible input current for current input (destruction limit), max. 30 mA; limited electronically
Cycle time (all channels) max. 40 ms; 33 to 40 ms
Input ranges
● Voltage No
● Current Yes
● Thermocouple No
● Resistance thermometer No
● Resistance No
Input ranges (rated values), currents
● 4 mA to 20 mA Yes; Into 25 Ohm
Cable length
● shielded, max. 200 m
Analog value generation for the inputs
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit; 4 to 20 mA: 13 bits
● Integration time, parameterizable Yes
● Integration time (ms) 16,67 / 20 ms
● Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
Smoothing of measured values
● parameterizable Yes; in 4 stages
● Step: None Yes; 1 x cycle time
● Step: low Yes; 4 x cycle time
● Step: Medium Yes; 16 x cycle time
● Step: High Yes; 32 x cycle time
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max. 750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.003 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %
Operational error limit in overall temperature range
● Current, relative to input range, (+/-) 0.4 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostic messages
● Wire-break Yes; Measuring range 1 to 5 V only
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 7 byte
Diagnostics wire break 1
Measurement type/range 1
Group diagnostics 1
Overflow/underflow 1
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ No
Isolation
Isolation tested with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight 40 g