Elit logo e-Elit - leading
electronic and automation component
online distributor
Est En
Elit shopping basket
Items: Total:
0
€0.00
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Analog Output Termination Assembly ControlLogix, simplex, Allen-Bradley
Analog Output Termination Assembly ControlLogix, simplex, Allen-Bradley



Siplus S7-300, SM331, 20pole medial stress w. conformal coating, based on 6ES7331-7SF00-0AB0 w.o. PTB approbation, Siemens
Image is illustrative
Siplus S7-300, SM331, 20pole medial stress w. conformal coating, based on 6ES7331-7SF00-0AB0 w.o. PTB approbation, Siemens
Code: 6AG1331-7SF00-4AB0
Price (indicative)
€1,369.20  /pc
Manufacturer :
Availability:
21 days
Weight:
0.2688 kg/pc
Volume:
0.001 m3/pc
Quantity (pc):
Plus sign Minus sign
 

 

Siplus S7-300, SM331, 20pole medial stress w. conformal coating, based on 6ES7331-7SF00-0AB0 w.o. PTB approbation, Siemens

Supply voltage
Load voltage L+
● Rated value (DC) 24 V
Input current
from backplane bus 5 V DC, max. 120 mA
Power loss
Power loss, typ. 0.6 W
Analog inputs
Number of analog inputs 8; 8x thermocouples; 4x RTD thermoresistors
Input ranges
● Voltage Yes
● Current No
● Thermocouple Yes
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), thermocouples
● Type B Yes
● Input resistance (Type B) 10 MΩ
● Type E Yes
● Input resistance (Type E) 10 MΩ
● Type J Yes
● Input resistance (type J) 10 MΩ
● Type K Yes
● Input resistance (Type K) 10 MΩ
● Type L Yes
● Input resistance (Type L) 10 MΩ
● Type N Yes
● Input resistance (Type N) 10 MΩ
● Type R Yes
● Input resistance (Type R) 10 MΩ
● Type S Yes
● Input resistance (Type S) 10 MΩ
● Type T Yes
● Input resistance (Type T) 10 MΩ
● Type U Yes
● Input resistance (Type U) 10 MΩ
Input ranges (rated values), resistance thermometer
● Ni 100 Yes
● Input resistance (Ni 100) 10 MΩ
● Pt 100 Yes
● Input resistance (Pt 100) 10 MΩ
● Pt 200 Yes
● Input resistance (Pt 200) 10 MΩ
Cable length
● shielded, max. 200 m; TC: 50 m
Analog value generation for the inputs
Measurement principle Sigma Delta
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit; 10 bit to 15 bit + sign
● Integration time, parameterizable Yes; 2.5 to 100 ms
● Interference voltage suppression for interference frequency f1 in Hz 10 to 400 Hz
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer Yes
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Temperature error (relative to input range), (+/-) Temperature error: 0.001 to 0.002 %/K
Operational error limit in overall temperature range
● Resistance thermometer, relative to input range, (+/-) 0.09 to 0.04%
Basic error limit (operational limit at 25 °C)
● Resistance thermometer, relative to input range, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 60 dB
● Common mode interference, min. 130 dB
Interrupts/diagnostics/status information
Diagnostic functions Yes
Diagnostic messages
● Diagnostic information readable Yes
● Overrange Yes
● Wire-break in signal transmitter cable Yes
● Short-circuit of the signal encoder cable Yes
Diagnostics indication LED
● Group error SF (red) Yes
● Channel fault indicator F (red) Yes
Ex(i) characteristics
Module for Ex(i) protection Yes
Maximum values of input circuits (per channel)
● Co (permissible external capacity), max. 43 µF
● Io (short-circuit current), max. 28.8 mA
● Lo (permissible external inductivity), max. 40 mH
● Po (power of load), max. 41.4 mW
● Uo (output no-load voltage), max. 5.9 V
Potential separation
Potential separation analog inputs
● Potential separation analog inputs Yes
Permissible potential difference
between the inputs (UCM) 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
Between the inputs and MANA (UCM) 60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area
Standards, approvals, certificates
CE mark Yes
UL approval Yes; File E239877
FM approval Yes; CofC 3028431
RCM (formerly C-TICK) Yes
KC approval Yes
EAC (formerly Gost-R) Yes
Railway application
● EN 50155 No
Use in hazardous areas
● Test number KEMA KEMA 09 ATEX 0077X
Ambient conditions
Ambient temperature during operation
● min. 0 °C; = Tmin
● max. 60 °C; = Tmax
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Ambient air temperature-barometric pressure-altitude Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
● With condensation, tested in accordance with IEC 60068-2-38, max. 100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
Resistance
Use in stationary industrial systems
— to biologically active substances according to EN 60721-3-3 Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna); Class 3B3 on request
— to chemically active substances according to EN 60721-3-3 Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— to mechanically active substances according to EN 60721-3-3 Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Connection method
required front connector 20-pin
Weights
Weight, approx. 210 g
last modified: 11/20/2017
 
 