|
|
|
Image is illustrative
|
DC/DC Converter MINI-PS-12-24DC/24DC/1, Phoenix Code:
2866284
Price
Manufacturer
:
Availability:
21 days
|
Weight:
0.0348 kg/pc
|
Volume:
0 m3/pc
|
|
|
|
|
DC/DC Converter MINI-PS-12-24DC/24DC/1, PhoenixDimensions
Width
|
22.5 mm
|
Height
|
99 mm
|
Depth
|
107 mm
|
Installation distance right/left
|
0 mm / 0 mm (≤ 70 °C)
|
Installation distance top/bottom
|
50 mm / 50 mm (≤ 70 °C)
|
Ambient conditions
Degree of protection
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
Input data
Nominal input voltage range
|
12 V DC ... 24 V DC
|
Input voltage range
|
10 V DC ... 32 V DC
|
Frequency range DC
|
0 Hz
|
Current consumption
|
2.6 A (12 V DC)
|
|
1.3 A (24 V DC)
|
Inrush current
|
< 15 A (typical)
|
Mains buffering time
|
typ. 3 ms (12 V DC)
|
|
typ. 20 ms (24 V DC)
|
Input fuse
|
6.3 A (slow-blow, internal)
|
Output data
Nominal output voltage
|
24 V DC ±1 %
|
Setting range of the output voltage (USet)
|
22.5 V DC ... 28.5 V DC (> 24 V DC, constant capacity restricted)
|
Nominal output current (IN)
|
1 A (-25 °C ... 60 °C)
|
Derating
|
60 °C ... 70 °C (2.5%/K)
|
Connection in parallel
|
yes, for assembling redundant systems and increasing efficiency
|
Connection in series
|
yes
|
Residual ripple
|
< 30 mVPP (20 MHz)
|
Output power
|
24 W
|
Typical response time
|
< 0.5 s
|
Peak switching voltages nominal load
|
< 100 mVPP (20 MHz)
|
Maximum power dissipation in no-load condition
|
< 1.2 W
|
Power loss nominal load max.
|
< 5 W
|
General
Net weight
|
0.2 kg
|
Operating voltage display
|
Green LED
|
Efficiency
|
> 83 % (at 24 V DC and nominal values)
|
MTBF (IEC 61709, SN 29500)
|
|
|
> 2569000 h (40 °C)
|
|
|
Insulation voltage input/output
|
1.5 kV (type test)
|
|
1 kV (routine test)
|
Degree of protection
|
IP20
|
Protection class
|
III
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: horizontally 0 mm, vertically 50 mm
|
Connection data, input
Connection method
|
Pluggable screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
14
|
Stripping length
|
7 mm
|
Screw thread
|
M3
|
Connection data, output
Connection method
|
Pluggable screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
14
|
Stripping length
|
7 mm
|
Screw thread
|
M3
|
Signaling
Output name
|
DC OK active
|
Output description
|
UOUT > 21.5 V: High signal
|
Maximum switching voltage
|
≤ 24 V DC
|
Output voltage
|
+ 24 V (Signal)
|
Continuous load current
|
≤ 20 mA
|
Status display
|
"DC OK" LED green
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
2.5 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
2.5 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
14
|
Tightening torque, min
|
0.5 Nm
|
Tightening torque max
|
0.6 Nm
|
Screw thread
|
M3
|
Standards
EMC requirements for noise immunity
|
EN 61000-6-1
|
|
EN 61000-6-2
|
EMC requirements for noise emission
|
EN 61000-6-3
|
|
EN 61000-6-4
|
Standard - Electrical safety
|
EN 60950-1/VDE 0805 (SELV)
|
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
|
EN 50178/VDE 0160 (PELV)
|
Standard - Safe isolation
|
DIN VDE 0100-410
|
Rail applications
|
EN 50121-4
|
Conformance/approvals
UL approvals
|
UL/C-UL listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
Shipbuilding approval
|
DNV GL (EMC A)
|
EMC data
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Low Voltage Directive
|
Conformance with Low Voltage Directive 2014/35/EC
|
Electrostatic discharge
|
EN 61000-4-2
|
Electromagnetic HF field
|
EN 61000-4-3
|
Fast transients (burst)
|
EN 61000-4-4
|
Surge voltage load (surge)
|
EN 61000-4-5
|
Conducted interference
|
EN 61000-4-6
|
Voltage dips
|
EN 61000-4-11
|
Environmental Product Compliance
REACh SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27210901
|
ECLASS 11.0 |
27210901
|
ECLASS 4.0 |
27210900
|
ECLASS 4.1 |
27210900
|
ECLASS 5.0 |
27210900
|
ECLASS 5.1 |
27210900
|
ECLASS 6.0 |
27210900
|
ECLASS 7.0 |
27210901
|
ECLASS 9.0 |
27210901
|
ETIM
ETIM 2.0 |
EC001039
|
ETIM 3.0 |
EC001039
|
ETIM 4.0 |
EC000599
|
ETIM 6.0 |
EC002046
|
ETIM 7.0 |
EC002046
|
UNSPSC
UNSPSC 6.01 |
30211502
|
UNSPSC 7.0901 |
39121004
|
UNSPSC 11 |
39121004
|
UNSPSC 12.01 |
39121004
|
UNSPSC 13.2 |
39121041
|
UNSPSC 18.0 |
39121041
|
UNSPSC 19.0 |
39121041
|
UNSPSC 20.0 |
39121041
|
UNSPSC 21.0 |
39121041
|
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|
|