Image is illustrative
|
Digital Interface Module ControlLogix® 1492, fixed terminal block, 20pin, 85..132VAC/VDC, Allen-Bradley Code:
1492-IFM20F-F120A-2
Price (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.338 kg/pc
|
Volume:
0.0022 m3/pc
|
|
|
|
|
Digital Interface Module ControlLogix® 1492, fixed terminal block, 20pin, 85..132VAC/VDC, Allen-Bradley
DESCRIPTIONS
-
ControlLogix® Digital Interface Module With Fixed Terminal Block, Amperage Rating: 2 A Per Circuit, 12 A Per Module, 1.2 MA Indicator Circuit, Voltage Rating: 85 - 132 VAC/VDC, Length: 4.72 IN, Width: 2.78 IN, Height: 3.27 IN, Connection Cables: 22 - 12 AWG, 20 Pin, Temperature Rating: 0 - 60 DEG C, Terminal Block Screw Torque: 3.5 - 4.5 LB-IN, Wire Strip Length: 0.32 IN, Environmental Conditions: 5 - 95% Non-Condensing Operating Humidity, Standard/Approvals: cUlus listed, CE marked, CSA certified, KC certified, NRTL certified, UL listed
SPECIFICATIONS
-
-
Item Name: Digital Interface Module With Fixed Terminal Block
-
Sub Brand: ControlLogix®
-
Amperage Rating: 2 A Per Circuit, 12 A Per Module, 1.2 MA Indicator Circuit
-
Voltage Rating: 85 - 132 VAC/VDC
-
Length: 4.72 IN
-
Width: 2.78 IN
-
Height: 3.27 IN
-
Connection Cables: 22 - 12 AWG, 20 Pin
-
Temperature Rating: 0 - 60 DEG C
-
Environmental Conditions: 5 - 95% Non-Condensing Operating Humidity
-
Terminal Block Screw Torque: 3.5 - 4.5 LB-IN
-
Wire Strip Length: 0.32 IN
FEATURES
-
Fusible modules provide a convenient method of adding overcurrent protections into your programmable controller wiring. These modules have 5 X 20 fuse holders on-board and are available with and without blown fuse indication. The 24, 120, and 240 V blown fuse indicators reduce the troubleshooting time to locate and replace a blown fuse on the IFM. Fusible modules have an easy-to-remove, transparent plexiglass cover that prevents objects from contacting fuse circuitry under normal operation. Removal of fuses from the standard fuse holder is aided by fuse pullers (fuses not provided). The fusible modules also have two or four terminals per I/O point to create a power bus for input and output load connections. Fusible modules are available in both isolated and nonisolated versions. There are a select number of fusible IFMs available for input modules. - 5 X 20 MM fuse clips with 120 V blown fuse indicators for input modules
- Two per Input/Output connection
- Standards: cUlus listed, CE marked, CSA certified, KC certified, NRTL certified, UL listed
|
|
|
|
|