Overview
ICL-16R/ICL-16L 16A AC inrush current limiter.
Features
Inrush current limiting: 23A.
AC input: 180..264VAC.
AC line frequency: 47..63Hz.
AC continuous rated current: 16A continuous.
Integrated bypass relay, no simple NTC.
Internal thermal protection.
DIN rail TS35/7.5 or TS35/15 (ICL-16R).
Working temperature: -30..+70°C.
3 years warranty.
Applications
Allow connecting multiple power supply at same line.
Allows smaller and faster circuit breaker.
Capacitive load.
Protects against unintended trigger of circuit breaker.
Specifications
| AC input power |
3680VA (16A x 230VAC) |
| AC input consumption |
<1.5W at 264VAC,50Hz input |
| Internal relay limiting time (ton power on) |
300±50ms |
| Internal relay release time |
500±50ms |
| Internal protection |
Thermal fuse protects overload and fire |
| Allowed capacitive load |
2500µF max. |
| Working humidity |
20..90%RH non-condensing |
| Storage temperature |
-40..+85°C |
| Operating altitude |
5000 meters |
| Over voltage category |
III, according to IEC62368-1, altitude up to 5000 meters |
| Pollution degree |
2 |
| Safety standards |
LVD BS EN/EN62368-1 approved |
| EMC emission |
Conducted: BS EN55032 Class B Radiated: BS EN55032 Class B Harmonic current: BS EN61000-3-2 Class A Voltage flicker: BS EN61000-3-3 |
Dimensions
| ICL-16R |
35x90x58.4mm |
| ICL-16L |
175x45x44.2mm |