G32A-EA 100-240AC| Accurax Linear Motor Axis, for use with SSR´s, Omron
G32A-EA 100-240AC| Accurax Linear Motor Axis, for use with SSR´s, Omron



Electronics Module ET 200S, output 8DO sink, 0.5A 24VDC, W15mm, Siemens
Pilt on illustreeriv
Electronics Module ET 200S, output 8DO sink, 0.5A 24VDC, W15mm, Siemens
Kood: 6ES7132-4BF50-0AA0
Hind (indikatiivne)
€ 46,50  /tk
Tootja :
Saadavus:
21 päeva
Kaal:
0.0441 kg/tk
Maht:
0.0001 m3/tk
Kogus (tk):
Plus sign Minus sign
 

 

Electronics Module ET 200S, output 8DO sink, 0.5A 24VDC, W15mm, Siemens

Electronics module for ET 200S, 8 DO Sink Output, 24 V DC/0.5 A, 15 mm width, 1 unit per packing unit
Supply voltage
Reverse voltage protection Yes; when using the same correctly polarized load voltage as on the power module
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 5 mA
from backplane bus 3.3 V DC, max. 10 mA
Power loss
Power loss, typ. 1.5 W
Address area
Address space per module
● without packing 1 byte
Digital outputs
Number of digital outputs 8
Short-circuit protection Yes
● Response threshold, typ. 1.5 A
Limitation of inductive shutdown voltage to Typ. 47 V
Controlling a digital input Yes
Switching capacity of the outputs
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 3 400 Ω
Output voltage
● for signal "1", min. Max. 1 V
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range, min. 5 mA
● for signal "1" permissible range, max. 600 mA
● for signal "0" residual current, max. 5 µA
Output delay with resistive load
● "0" to "1", max. 300 µs
● "1" to "0", max. 600 µs
Parallel switching of two outputs
● for uprating No
● for redundant control of a load Yes; per module
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per module, max. 4 A
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
Interrupts/diagnostics/status information
Diagnostics function No
Diagnostics indication LED
● Status indicator digital output (green) Yes
Parameter
Remark 3 byte
Potential separation
Potential separation digital outputs
● between the channels No
● between the channels and backplane bus Yes
Isolation
Isolation tested with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g