Sitop Select, Diagnostics Module, 4-ch., input 40A 24VDC, output 4x 10A (adj. 2..10A) 24VDC, Siemens
Pilt on illustreeriv
Sitop Select, Diagnostics Module, 4-ch., input 40A 24VDC, output 4x 10A (adj. 2..10A) 24VDC, Siemens
Kood: 6EP1961-2BA00
Hind (indikatiivne)
€ 148,90  /tk
Tootja :
Saadavus:
21 päeva
Kaal:
0.42 kg/tk
Maht:
0.001 m3/tk
Kogus (tk):
Plus sign Minus sign
 

 

Sitop Select, Diagnostics Module, 4-ch., input 40A 24VDC, output 4x 10A (adj. 2..10A) 24VDC, Siemens

SITOP SELECT DIAGNOSIS MODULE
SITOP select Diagnostics module 4-channel input: 24 V DC/40 A output: 24 V DC/4x 10 A Level adjustable 2-10 A
Input
Type of the power supply network Controlled DC voltage (SITOP select is not designed for operation with DC UPS module 40 A (6EP1 931-2FC21/-2FC42)
Supply voltage / at DC / Rated value 24 V
Input voltage / at DC 22 ... 30 V
Overvoltage overload capability 35 V; 100 ms
Input current / at rated input voltage 24 V / Rated value 40 A
Output
Voltage curve / at output controlled DC voltage
Formula for output voltage Vin - approx. 0.3 V
Relative overall tolerance / of the voltage / Note In accordance with the supplying input voltage
Number of outputs 4
Output current / up to 60 °C / per output / rated value 10 A
Adjustable pick-up value current / of the current-dependent overload release 2 ... 10 A
Type of response value setting via potentiometer
Product feature / parallel switching of outputs No
Product feature / bridging of equipments Yes
Type of outputs connection Simultaneous connection of all outputs after power up of the supply voltage, delay time of 24 ms or 100 ms programmable for sequential connection
Efficiency
Efficiency in percent 97 %
Power loss [W] / at rated output current / for rated value of the output current / typical 30 W
Switch-off characteristic per output
Switching characteristic
● of the excess current Iout = 1.0 ...1.3 x set value, switch-off after approx. 5 s
● of the current limitation Iout = 1.3 x set value, switch-off after approx. 50 ... 100 ms
● of the immediate switch-off Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms
Residual current at switch-off / typical 20 mA
Design of the reset device/resetting mechanism Using keys on the module
Remote reset function -
Protection and monitoring
Fuse protection type / at input Blade-type fuse per output (equipped when delivered with 15 A fuse)
Display version / for normal operation Two-color LED per output: green LED for "Output switched through"; red LED for "Output switched off due to overcurrent"
Design of the switching contact / for signaling function Common signal contact (NO contact, rating 0.5 A/24 V DC)
Safety
Galvanic isolation / between input and output at switch-off No
Operating resource protection class Class III
Certificate of suitability
● CE marking Yes
● as approval for USA UL-Recognized (UL 2367) File E328600; cULus-Listed (UL 508, CSA C22.2 No. 107.1) File E197259; cURus (UL 60950, CSA C22.2 No. 60950) File E151273
Standard / for safety according to EN 60950-1 and EN 50178
Certificate of suitability / relating to ATEX ATEX (EX) II 3G Ex nAC IIC T4 U; cCSAus Class I, Div. 2, Group ABCD, T4
Protection class IP IP20
EMC
Standard
● for emitted interference EN 55022 Class B
● for interference immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation 0 ... 60 °C
— Note with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
Environmental category / acc. to IEC 60721 Climate class 3K3, no condensation
Mechanics
Type of electrical connection screw-type terminals
● at input +24 V: 2 screw terminals for 0.5 ... 16 mm²; 0 V: 2 screw terminals for 0.5 ... 4 mm²
● at output Output 1 ... 4: 1 screw terminal each for 0.22 ... 4 mm²
● for signaling contact 2 screw terminals for 0.22 ... 4 mm²
● for auxiliary contacts -
Width / of the enclosure 72 mm
Height / of the enclosure 90 mm
Depth / of the enclosure 90 mm
Installation width 72 mm
Mounting height 190 mm
Net weight 0.4 kg
Mounting type Snaps onto DIN rail EN 60715 35x7.5/15
Product component / belonging to 4x blade-type fuse 15 A
MTBF / at 40 °C 378 928 h
Other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
 
 