Pilt on illustreeriv
|
High-current Terminal UKH 50, 10pcs/pck, Phoenix Kood:
3009118
Hind
€ 147,00
/pk
Package 10tk, unit price
14.7EUR/tk
Tootja
:
Saadavus:
21 päeva
|
Kaal:
0.1191 kg/tk
|
Maht:
0.0002 m3/tk
|
|
|
|
|
High-current Terminal UKH 50, 10pcs/pck, PhoenixGeneral
Number of rows
|
1
|
Number of connections
|
2
|
Potentials
|
1
|
Nominal cross section
|
50 mm²
|
Color
|
gray
|
Insulating material
|
PA
|
Flammability rating according to UL 94
|
V0
|
Mounting type
|
NS 35/7,5
|
Rated surge voltage
|
8 kV
|
Degree of pollution
|
3
|
Overvoltage category
|
III
|
Insulating material group
|
I
|
Maximum load current
|
150 A (with 50 mm² conductor cross section)
|
Nominal current IN
|
150 A
|
Nominal voltage UN
|
1000 V
|
Open side panel
|
No
|
Shock protection test specification
|
DIN EN 50274 (VDE 0660-514):2002-11
|
Back of the hand protection
|
guaranteed
|
Finger protection
|
guaranteed
|
Note regarding shock protection
|
Finger-safe protection is not guaranteed if bridges are positioned.
|
Result of surge voltage test
|
Test passed
|
Result of power-frequency withstand voltage test
|
Test passed
|
Power frequency withstand voltage setpoint
|
2.2 kV
|
Result of the test for mechanical stability of terminal points (5 x conductor connection)
|
Test passed
|
Result of flexion and pull-out test
|
Test passed
|
Bending test rotation speed
|
10 rpm
|
Bending test turns
|
135
|
Bending test conductor cross section/weight
|
25 mm² / 4.5 kg
|
|
50 mm² / 9.5 kg
|
Tensile test result
|
Test passed
|
Conductor cross section tensile test
|
25 mm²
|
Tractive force setpoint
|
135 N
|
Conductor cross section tensile test
|
50 mm²
|
Tractive force setpoint
|
236 N
|
Conductor cross section tensile test
|
70 mm²
|
Tractive force setpoint
|
285 N
|
Result of tight fit on support
|
Test passed
|
Tight fit on carrier
|
NS 32/NS 35
|
Setpoint
|
10 N
|
Result of voltage-drop test
|
Test passed
|
Requirements, voltage drop
|
U1 ≤ 3.2 mV; U2 ≤ 1.5 x U1
|
Result of temperature-rise test
|
Test passed
|
Requirement temperature-rise test
|
Increase in temperature ≤ 45 K
|
Short circuit stability result
|
Test passed
|
Conductor cross section short circuit testing
|
50 mm²
|
Short-time current
|
6 kA
|
Result of thermal test
|
Test passed
|
Proof of thermal characteristics (needle flame) effective duration
|
30 s
|
Relative insulation material temperature index (Elec., UL 746 B)
|
130 °C
|
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
|
130 °C
|
Static insulating material application in cold
|
-60 °C
|
Surface flammability NFPA 130 (ASTM E 162)
|
passed
|
Specific optical density of smoke NFPA 130 (ASTM E 662)
|
passed
|
Calorimetric heat release NFPA 130 (ASTM E 1354)
|
28 MJ/kg
|
Smoke gas toxicity NFPA 130 (SMP 800C)
|
passed
|
Fire protection for rail vehicles (DIN EN 45545-2) R22
|
HL 1 - HL 3
|
Fire protection for rail vehicles (DIN EN 45545-2) R23
|
HL 1 - HL 3
|
Fire protection for rail vehicles (DIN EN 45545-2) R24
|
HL 1 - HL 3
|
Fire protection for rail vehicles (DIN EN 45545-2) R26
|
HL 1 - HL 3
|
Dimensions
Width
|
20 mm
|
Length
|
70.5 mm
|
Height
|
76 mm
|
Height NS 35/15
|
83.5 mm
|
Height NS 32
|
81 mm
|
Connection data
Connection method
|
Screw connection
|
Screw thread
|
M6
|
Stripping length
|
24 mm
|
Tightening torque, min
|
6 Nm
|
Tightening torque max
|
8 Nm
|
Connection in acc. with standard
|
IEC 60947-7-1
|
Note
|
Note: Product releases, connection cross sections and notes on connecting aluminum cables can be found in the download area.
|
Conductor cross section solid min.
|
16 mm²
|
Conductor cross section solid max.
|
70 mm²
|
Conductor cross section AWG min.
|
6
|
Conductor cross section AWG max.
|
2/0
|
Conductor cross section flexible min.
|
25 mm²
|
Conductor cross section flexible max.
|
70 mm²
|
Min. AWG conductor cross section, flexible
|
3
|
Max. AWG conductor cross section, flexible
|
2/0
|
Conductor cross section flexible, with ferrule without plastic sleeve min.
|
25 mm²
|
Conductor cross section flexible, with ferrule without plastic sleeve max.
|
50 mm²
|
Conductor cross section flexible, with ferrule with plastic sleeve min.
|
25 mm²
|
Conductor cross section flexible, with ferrule with plastic sleeve max.
|
50 mm²
|
2 conductors with same cross section, solid min.
|
10 mm²
|
2 conductors with same cross section, solid max.
|
16 mm²
|
2 conductors with same cross section, stranded min.
|
10 mm²
|
2 conductors with same cross section, stranded max.
|
16 mm²
|
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum
|
10 mm²
|
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum
|
16 mm²
|
Internal cylindrical gage
|
B10
|
Ambient conditions
Operating temperature
|
-60 °C ... 105 °C (max. short-term operating temperature 125°C)
|
Ambient temperature (storage/transport)
|
-25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
|
Permissible humidity (storage/transport)
|
30 % ... 70 %
|
Ambient temperature (assembly)
|
-5 °C ... 70 °C
|
Ambient temperature (actuation)
|
-5 °C ... 70 °C
|
Standards and Regulations
Connection in acc. with standard
|
CSA
|
|
IEC 60947-7-1
|
Flammability rating according to UL 94
|
V0
|
Environmental Product Compliance
China RoHS
|
Environmentally friendly use period: unlimited = EFUP-e
|
|
No hazardous substances above threshold values
|
ECLASS
ECLASS 10.0.1 |
27141120
|
ECLASS 11.0 |
27141120
|
ECLASS 4.0 |
27141100
|
ECLASS 4.1 |
27141100
|
ECLASS 5.0 |
27141100
|
ECLASS 5.1 |
27141100
|
ECLASS 6.0 |
27141100
|
ECLASS 7.0 |
27141120
|
ECLASS 9.0 |
27141120
|
ETIM
ETIM 2.0 |
EC000897
|
ETIM 3.0 |
EC000897
|
ETIM 4.0 |
EC000897
|
ETIM 6.0 |
EC000897
|
ETIM 7.0 |
EC000897
|
UNSPSC
UNSPSC 6.01 |
30211811
|
UNSPSC 7.0901 |
39121410
|
UNSPSC 11 |
39121410
|
UNSPSC 12.01 |
39121410
|
UNSPSC 13.2 |
39121410
|
UNSPSC 18.0 |
39121410
|
UNSPSC 19.0 |
39121410
|
UNSPSC 20.0 |
39121410
|
UNSPSC 21.0 |
39121410
|
|