e-Elit - juhtiv
elektri- ja automaatikatarvikute
online hulgimüük
Klienditeenindus E-R 9-17
Helista: +372 622 9119
Est En
Elit shopping basket
Tooteid: Maksumus:
0
€ 0,00
    search
Logi sisse
Kasutajatunnus/e-post:

Parool:

Näita kõiki kategooriaid
Ei leidnud sobilikku toodet?
Head pakkumised!



Monitoring Relay EMD-FL-3V-400, Phoenix
Pilt on illustreeriv
Monitoring Relay EMD-FL-3V-400, Phoenix
Kood: 2866064
Hind
€ 298,70  /tk
Tootja :
Saadavus:
21 päeva
Kaal:
0.1722 kg/tk
Maht:
0.0002 m3/tk
Kogus (tk):
Plus sign Minus sign
 

 

Monitoring Relay EMD-FL-3V-400, Phoenix

Note

Utilization restriction EMC: class A product, see manufacturer's declaration in the download area

Dimensions

Width 22.5 mm
Height 90 mm
Depth 113 mm

Ambient conditions

Ambient temperature (operation) -25 °C ... 55 °C
-25 °C ... 40 °C (corresponds to UL 508)
Ambient temperature (storage/transport) -25 °C ... 70 °C
Permissible humidity (operation) 15 % ... 85 %
Degree of protection IP40 (Housing)
IP20 (Connection terminal blocks)
Noise immunity EN 61000-6-2

Input data

Nominal input voltage UN 3 N ~ 400/230 V
Maximum temperature coefficient < 0.1 %/K
Function Undervoltage, window, asymmetry, phase sequence, phase failure
Min. setting range -30 % ... 20 % (From UN)
Max. setting range -20 % ... 30 % (From UN)
Min setting range of the voltage threshold value 280 V AC ... 480 V AC
Max. setting range of the voltage threshold value 320 V AC ... 520 V AC
Setting range for response delay 0.1 s ... 10 s
Basic accuracy ± 5 % (of scale end value)
Setting accuracy ≤ 5 % (of scale end value)
Repeat accuracy ≤ 2 %
Asymmetry 5 % ... 25% / OFF
Recovery time 500 ms

Contact side

Contact type 2 floating changeover contacts
Maximum switching voltage 250 V AC (in acc. with IEC 60664-1)
Interrupting rating (ohmic load) max. 750 VA (3 A/250 V AC, module aligned, ≤ 5 mm spacing)
1250 VA (5 A/250 V AC, module not aligned, ≥ 5 mm spacing)
Output fuse 5 A (fast-blow)

Power supply

Supply voltage 230 V AC
24 V DC
Supply voltage range 24 V AC ... 240 V AC -15 % ... +10 %
24 V DC ... 240 V DC -20 % ... +25 %

General

Mechanical service life approx. 2x 107 cycles
Operating mode 100% operating factor
Mounting position any
Assembly instructions on standard DIN rail NS 35 in accordance with EN 60715
Electromagnetic compatibility Conformance with EMC directive
Housing insulation material Polyamide PA, self-extinguishing
Color green

Connection data

Connection method Screw connection
Stripping length 8 mm
Conductor cross section solid 0.5 mm² ... 2.5 mm²
Conductor cross section flexible 0.25 mm² ... 2.5 mm²
Conductor cross section AWG 20 ... 14
Tightening torque 1 Nm

Standards and Regulations

Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity EN 61000-6-2
Standards/regulations EN 50178
Rated insulation voltage 300 V
Insulation Basic insulation
Pollution degree 2
Overvoltage category III
Low Voltage Directive Conformance with Low Voltage Directive

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

ECLASS

ECLASS 10.0.1 27371801
ECLASS 11.0 27371801
ECLASS 4.0 27371100
ECLASS 4.1 27371100
ECLASS 5.0 27371800
ECLASS 5.1 27371800
ECLASS 6.0 27371800
ECLASS 7.0 27371801
ECLASS 9.0 27371801

ETIM

ETIM 2.0 EC001438
ETIM 3.0 EC001438
ETIM 4.0 EC001438
ETIM 6.0 EC001438
ETIM 7.0 EC001438

UNSPSC

UNSPSC 6.01 30211916
UNSPSC 7.0901 39121535
UNSPSC 11 39121535
UNSPSC 12.01 39121535
UNSPSC 13.2 41113620
UNSPSC 18.0 41113620
UNSPSC 19.0 41113620
UNSPSC 20.0 41113620
UNSPSC 21.0 41113620
 
 
Elit OÜ | e-post: elit@elit.ee | +372 622 9119 | 2021 ©


 
X
 
X