|
|
Pilt on illustreeriv
|
Analog Input Module ControlLogix, 16-ch., input 0/4..20mA, 200mA 5V drawn, Allen-Bradley Kood:
1756-IF16H
Hind (indikatiivne)
Tootja
:
Saadavus:
küsi tarneaega
|
Kaal:
0.361 kg/tk
|
Maht:
0.0022 m3/tk
|
|
|
|
|
Analog Input Module ControlLogix, 16points HART, Rockwell Automation
ControlLogix® Analog Input Module, Number Of Channels: 16 (Differential), Input: 0 - 20 MA, 4 - 20 MA, Voltage Rating: Overvoltage Protection: 8 VDC, Current Rating: Drawn: 200 MA At 5 V, 125 MA At 24 V, Isolation: 50 V (Continuous), Basic Insulation Type, Inputs-To-Backplane, No Isolation Between Individual Inputs, Type Tested At 1500 VDC For 60 SEC, Power Rating: Backplane: 4.02 W, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 1 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ On Shielded Signal Ports, Display: Module Health, In Calibration Mode, Interface: Removable Terminal Block, IEEE, Mounting: Chassis, Temperature Rating: 32 - 140 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G At 10 - 500 HZ , Shock: 30 G(Operating), 50 G (Non-Operating), Response Time: Open Circuit Detection Time: Positive Full Scale Reading Within 5 SEC, Module Input Scan Time: 11 - 328 MS, Module HART Scan Time: Typically 1 SEC, Accuracy: Better Than 0.13% Of Range, Power Dissipation: 6 W, Impedance: Input: 249 OHM, Slot Width: 1, Surge Transient Immunity: Plus/Minus 2 KV Line-Earth (CM) On Shielded Signal Ports, Resolution: 16 - 21 Bits, Standard/Approvals: C/US UL listed, CE-ATEX marked, CE-EMC marked, C-TICK certified, GOST_R certified, KCC certified, ROSTECHNADZOR
|
|
Specifications
- Item Name: Analog Input Module
- Sub Brand: ControlLogix®
- Number Of Channels: 16 (Differential)
- Input: 0 - 20 MA, 4 - 20 MA
- Voltage Rating: Overvoltage Protection: 8 VDC
- Current Rating: Drawn: 200 MA At 5 V, 125 MA At 24 V
- Isolation: 50 V (Continuous), Basic Insulation Type, Inputs-To-Backplane, No Isolation Between Individual Inputs, Type Tested At 1500 VDC For 60 SEC
- Power Rating: Backplane: 4.02 W
- Enclosure: Open Type
- Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 1 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ On Shielded Signal Ports
- Display: Module Health, In Calibration Mode
- Interface: Removable Terminal Block, IEEE
- Mounting: Chassis
- Temperature Rating: 32 - 140 DEG F
- Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G At 10 - 500 HZ , Shock: 30 G(Operating), 50 G (Non-Operating)
- Response Time: Open Circuit Detection Time: Positive Full Scale Reading Within 5 SEC, Module Input Scan Time: 11 - 328 MS, Module HART Scan Time: Typically 1 SEC
- Accuracy: Better Than 0.13% Of Range
- Power Dissipation: 6 W
- Surge Transient Immunity: Plus/Minus 2 KV Line-Earth (CM) On Shielded Signal Ports
- Resolution: 16 - 21 Bits
- Impedance: Input: 249 OHM
- Slot Width: 1
Features
HART interface
Standards: C/US UL listed, CE-ATEX marked, CE-EMC marked, C-TICK certified, GOST_R certified, KCC certified, ROSTECHNADZOR
|
|
|
|