Pilt on illustreeriv
|
Analog Interface Module, Fusible 16-ch. analog IFM, 24V blown fuse indicators, 5 terminals per input, Allen-Bradley Kood:
1492-AIFM16-F-5
Hind (indikatiivne)
Tootja
:
Saadavus:
21 päeva
|
Kaal:
0.585 kg/tk
|
Maht:
0.0036 m3/tk
|
|
|
|
|
Analog Interface Module, Fusible 16-ch. analog IFM, 24V blown fuse indicators, 5 terminals per input, Allen-Bradley
DESCRIPTIONS
-
ControlLogix® Analog Interface Module With Fixed Terminal Block, Amperage Rating: 2 A Per Circuit, 12 A Per Module, 2 MA Indicator Circuit, Voltage Rating: 10 - 30 VDC, Length: 8.27 IN, Width: 2.74 IN, Height: 3.27 IN, Connection Cables: 22 - 12 AWG D-Shell Cable, Temperature Rating: 0 - 60 DEG C, Terminal Block Screw Torque: 3.5 - 4.5 LB-IN, Wire Strip Length: 0.32 IN, Environmental Conditions: 5 - 95% Non-Condensing Operating Humidity, Standard/Approvals: cUlus listed, CE marked, CSA certified, KC certified, NRTL certified, UL listed
SPECIFICATIONS
-
-
Item Name: Analog Interface Module With Fixed Terminal Block
-
Sub Brand: ControlLogix®
-
Amperage Rating: 2 A Per Circuit, 12 A Per Module, 2 MA Indicator Circuit
-
Voltage Rating: 10 - 30 VDC
-
Length: 8.27 IN
-
Width: 2.74 IN
-
Height: 3.27 IN
-
Connection Cables: 22 - 12 AWG D-Shell Cable
-
Temperature Rating: 0 - 60 DEG C
-
Environmental Conditions: 5 - 95% Non-Condensing Operating Humidity
-
Terminal Block Screw Torque: 3.5 - 4.5 LB-IN
-
Wire Strip Length: 0.32 IN
FEATURES
-
Fusible analog interface input modules provide a convenient method to fuse the input power source on the field side. The field-side power source is distributed through individual on-board 5 X 20 fuse holders. The AIFMs have a 24 VDC blown fuse indicators to reduce the troubleshooting time required to locate and replace a blown fuse. Fusible modules have an easy-to-remove transparent plexiglass cover to prevent objects from contacting fuse circuitry under normal operation. Standard fuse holders reside in the IFM, aiding in the removal of a fuse with a fuse puller (fuses are not included). Isolation switch plugs, or “dummy fuses”, are also available to isolate an input circuit once power is removed. In addition, once the circuit has been isolated and power restored, the input loop current can be measured in 2-wire transmitter applications. The fusible modules also have three or five terminals per I/O analog input point to create a power bus for device shield and power connections. - 16 input channels
- 5 X 20 MM fuse clips with 24 VDC blown fuse indicators for output modules
- 5 per input channel field-side wiring terminal
- Standards: cUlus listed, CE marked, CSA certified, KC certified, NRTL certified, UL listed
|
|
|
|
|